ELECTRICITY SUPPLY REGULATIONS
(SECTION-VIII)
THEFT OF ENERGY, MALPRACTICES, LEVY OF COMPENSATION
AND RECONNECTION OF SUPPLY |
 |
131. THEFT AND LESS RECORDING OF ENERGY-REMEDIAL MEASURES:
131.1 Under Section 39 of the Indian Electricity Act,1910, whoever dishonestly
abstract, consumers or uses any energy or where artificial means or means not
authorized by the Board exist for abstraction, consumption or use of energy,
shall be deemed to have committed theft within the meaning of the Indian Penal
Code..
131.2 Inspecting Officer shall check the MDI, KVAH and KWH meters alongwith
metering CTs and PTs as one unit and record reading as well as their
observations regarding functioning of each of these metering equipment units. It shall also be ensured that each and every meter alongwith
ancillary/allied equipment has been properly sealed, CTs and PTs with correct
matching specifications have been installed in accordance with wiring diagram of
the equipment and the multiplication factor etc., wherever applicable has been
properly taken care of while recording readings/observations.
131.3 Prevention of Theft of Electricity: Measures mentioned hereunder
will help in curbing the menace of Theft of Energy.
131.4 Curbing Theft direct from mains, service line, meter terminals:
Measures to counter the pilferage of electricity direct from the supply
mains/service line are as under:-
131.4.1 Cut outs should be provided after the meter instead of before the meter. In other words, the service line should be connected direct to the meter
and the cut-out should be provided on the load side. The main Board supporting
the meter should be properly grouted and its supporting bolds should be sealed. Meter terminal cover should also be sealed.
131.4.2 No P.T. fuses should be provided on the secondary side of the supply to
KWH/MDI meters. In the cases of existing connections, arrangements should be
made to remove the P.T. Fuses immediately.
131.4.3 Fuses, if any, provided by mistake on the secondary side of CT circuit
should be removed immediately.
131.5 In order to avoid reversal of connections it must be ensured that correct
connections are made at the merits terminals and its cover is properly sealed. Whenever meter terminal seal is broken or is found to be broken it must
be replaced at the earliest. Before
resealing it should be ensured that the connections are in order.
131.5.1 The connections , as such, should be checked by a responsible Engineering
Officer to ensure their correctness and working of the meter on each phase may
also be checked with the heater/water load, the equipment should thereafter be
sealed properly by the officer to whom the job has been assigned as per standing
instructions on the subject.
131.5.2 Connection wiring diagram of different types of metering equipments both
11 KV and LT as in use in PSEB should be circulated amongst the operation
engineering officers for their guidance.
131.6 Avoiding access to CTs/PTs and connecting wiring: For preventing
free access to weak links of metering equipment and to avoid tampering of CT.PT
connections for the purpose of theft of energy, remedial measures as under may
be taken.
131.6.1 The MC and CTs/PTs chambers
of standard design with proper construction as approved by the Board must be got
installed separately for meters and CTs/PTs. The meters in case of all industrial connections should be installed in
the MCBs of standard/approved design. No
connection should be released without the installation of such chambers. In no case unstandard chambers be accepted from the consumers. In case of existing connections the non standard MCBs and CT/PT chambers
should be replaced with MCBs and CT/PT chambers of approved design in a phased
manner.
131.6.2 In respect of Metering for LS/BS consumers where CTs/PTs are involved,
the test terminal block where provided, meter terminal cover and CTs/PTs chamber
need to be sealed carefully and properly by the Ops. officers who have been
assigned the job of sealing such metering equipment as per instructions contained in Regn. No.63. Such seals should not be broken without(a) the knowledge of the sealing
officer/official, (b) keeping a proper record of broken seals. Seals should be affixed expeditiously as and when the same have to be
broken for attending to faults etc. The
metering equipment in case of other industrial connections should also be sealed
properly and expeditiously by the competent authority.
131.6.3 The entry and exist holes for the cable in CT/PT chamber should be
plugged by putting suitable size of cable glands.
131.6.4 There should be no extra joint in the CT/PT extension leads and the
length of the leads should be limited to the minimum required. The joints between the extension leads of CTs and leads connecting the
meter should be crimped so as to have solid joints. The portion of CT leads having joints should be kept in the CT chamber
and must not be placed in the MCB portion. PT leads without any joint should be soldered/crimped on each phase of
the PSEB service cable so as to achieve solid connections. MCB and CT/PT chambers need to be placed adjacent to each other and the
CT/PT lead should pass through the GI Pipe welded on the CT Chamber and
connected to the MCB in such a way that the leads are not accessible to the
consumers. Drawing depicting the
correct arrangement should be circulated to the concerned officers.
131.6.5 The length of extension leads of the CTs/PTs should be sufficient for
taking to the meter terminal block to eliminate joints which when loose are
susceptible to carbonization or oxidation resulting into less recording of
energy. The wires should preferably
be of red , yellow, blue and black colours for clear distinction and to
facilitate quick checking. The
suppliers may be asked for making provisions of sufficient lengths of extension
leads in the CTs/PTs.
131.6.6 Combined CT/PT units must be installed for all HT metering equipment and
their covers should be sealed properly so as to avoid access to the connections. Separate CTs outside the combined unit must not be installed
under any circumstances.
131.7 Avoiding loose joints in CT/PT chambers and expeditious sealing:
As per practice in the field, consumer's main cable is connected to the
PSEB main service cable inside the CT chamber in case of LT metering. CT/PT chamber being of close construction and joint being a weak link in
the cable tends to heat up and the heat is not dissipated to the atmosphere, it ultimately results in over-hauling the joint and causes
damage to it. CT/PT chamber seals
are broken frequently in order to attend to the complaints of failure of supply
due to over heating and damage to the joints. Such seals are not affixed promptly and sometimes they are not affixed
for weeks/months together. Thus
over-heating and damage to the joints and consequently breaking of CT/PT chamber
seals allows to the unscrupulous consumers a free access to the CT/PT
connections for indulging in theft of electricity by tampering with the CT/PT
connections.
131.8 In order to avoid disengagement of potential leads which are connected at
the joints following measures may be taken:-
131.8.1 Remedial measures: The joint between PSEB service cable and consumer's
main cable should be taken out of the CT/PT chamber on load side. For the
existing connections these maybe done in a phased manner, and for new
connections, the joints must be made outside CT/PT chamber at the time of
releasing the connections. Drawing showing correct arrangement should be circulated to
the concerned officers from time to time.
131.8.2 The PT connections should be made by cutting insulating material of each
phase of PSEB Service Cable inside the CT/PT chamber and these maybe soldered so
as to ensure solid connections.
131.9 Measures to avoid fake seals etc:- To avoid Theft of electricity
through tampering/providing fake M&T seals, tampering meter window glass
fixing mechanism and providing small hold in the body of the meter, measures as
under are required to be taken:-
131.9.1 The instructions regarding affixing paper seals maybe rigidly followed by
all the officials/officers concerned.
131.9.2 Impression of ME seals may be stamped on the corners of the meter index
plate with indelible ink so that it can not be rubbed off.
131.9.3 ME seals should be of multifarious impressions and should be properly
pressed by using the latest technique like hydraulic pressing etc. The sealer with hydraulic pressing dies should be kept in steel chamber
in ME Lab having double locking arrangements. In no case, the officers/officials should be allowed to have access to
sealing-pliers/hydraulic pressing dies after the office hours or during
holidays.
131.9.4 M&T seals of the meters transferred from the jurisdiction of one ME
Lab to other should be replaced by the ME Lab in whose area meters are to be
installed . No sealer for M&T seals should move with the employee
even on transfer and should be kept in a locker with double key system to be
maintained in the office of ME Sub-Divn.
131.9.5 Energy meters with tampered/fake M&T seals or small holes made in the
meter body for the purpose of stealing electricity are replaced indiscriminately
by declaring such meters defective with ulterior motives after a short interval
of time so as to avoid detection of such malpractices. These meters are returned to ME Lab. after a long period for repairs and
recalibration. Remedial measures
against such a course of action are:-
131.9.5.1 Detailed investigations must be carried out in each and every case before
the meter is dismantled with one or the other plea so as to curb the tendency of
indiscriminate replacement of tampered meters. Action as per Condition No.43 of
the Conditions of Supply, where called for, should be taken immediately, failing
which action should be initiated against the officer/official who removed the
meter.
131.9.5.2 The meters which are declared defective and are removed must be returned
to ME/S/Divn. within a maximum period of 10 days in case of industrial meters
and one month in the case of general consumers.
131.9.5.3 Test results of defective meters, before their repair and recalibration,
should be obtained and recorded. The
cause of defect should also be established and recorded. Genuineness of M&T seals should also be checked and recorded.
131.9.6 The cases of premises 'locked' and 'Nil' consumption be got investigated
by the AE/AEE(Ops).
131.10. Energy Consumption Variation register: Careful examination/study
of cases of low and appreciable variation in energy consumption should provide
clues for investigating theft of electricity cases. In order to have an effective control/check over the mal-functioning of
the meters/theft of energy by properly maintaining/monitoring energy variations
registers for different category of consumers, following guidelines shall be
implemented strictly.
131.10.1 Maintenance of the Registers:
Officials/Officers responsible for maintaining energy variation register
shall be as under:-
i) GSC(DS and NRS) : Revenue Supdt RA/ARA
ii) SP/MS/Street Lighting : AAE or JE where AAE is not posted.
iii)LS/BS : AE./AEE/XEN Incharge of Ops./Divn
and AEE./Comml. in
case of Special
Division.
131.10.2 Procedure to be adopted for checking energy variation: For
keeping check on energy variation of various categories, consumption of a
particular month shall be compared with consumption of the same month of the
preceding year/average consumption of the preceding year/season and if there is
variation of ±10% in case of LS/BS consumer, ± 20% in case of MS/SP/Street
Lighting and ± 25% in case of GSC
category of consumers, the same shall be recorded on the energy variation
register already in vogue(CA-110) and necessary investigation carried out so as
to ascertain reasons for the said variation. Centralised Billing Cell, preparing
bills of Large Supply/Bulk Supply (more than 100 KW) consumes, shall also look
into variation(± 10%) in case of LS/BS consumers and shall submit the list
alongwith their comments to the respective operation sub-divisions for carrying
out further investigation. Similar
kind of industries shall be entered in the variation register separately for
relative consumption comparison.
Officers/officials responsible for maintenance of registers as per
131.10.1 above shall put up the same to AE./AEE/XEN Incharge of the sub-division
for necessary action being over all responsible for compliance of instructions.
131.10.3 Issue of Energy Variation Register:
Three separate registers as mentioned under Para-131.10.1 above be
maintained in each sub-division. These
registers duly numbered and attested by the Divn. Supdt. shall be issued by the
operation Division and record shall be maintained like SMBS Sr.XEN/Addl.SEs(Ops)
Incharge of (Ops) Division shall check/append initials on the registers while on
tour for ensuring compliance of these instructions.
131.11 Proper installation of meters: Observance of the ;provisions of
Regn. No.62 regarding installation of meters at proper place near the main
entrance of the consumer's premises should be rigidly followed. Measures as mentioned hereunder will be useful:
131.11.1 Release of new Large Industrial/Bulk Supply Connection: No new
large supply/bulk supply connection shall be released unless the consumer
provides a separate room as pr specifications and design prescribed by the Board
adjacent to the main entry gate for installation of metering equipment. The key of the room shall remain with the consumer and shall be available
at the gate to facilitate meter reading/checking by the PSEB officers/officials.
131.12. Measures as under may be taken to avoid pilferage of electricity from
the terminals of the Transformer installed at the consumer's premises:
131.12.1 The naked LT terminals of the distribution transformers including that of
the cable may be empire taped properly and thereafter these joints may be
provided with paper seals with the signatures of the SR.XEN/ASE and SE/Dy.CE/Ops
. These paper seals may be protected against any type of damage
by providing transparent plastic paper suitably.
131.13 M&T seals to remain intact: It should be ensured that the
consumer is not allowed to tamper with the M&T seal which encloses the
metering mechanism. Keeping a watch over the consumption of the consumer of the
consumer and checking the same with the theoretical consumption or the
consumption of similar consumers can give a clue as to whether there is a
possibility of the cyclometer of the mechanism having been changed. Normally such mischief will be possible in connivance with the trained
staff of the Board. It will, therefore, be useful if the meters of the consumers
are periodically checked/replaced.
131.14 Proper Transportation of meters: Rough and mishandling of energy
meters during transportation adversely effects the accuracy. To safeguard against this eventuality, wooden boxes, which are available
for packing energy meters should be used for transporting meters from stores/ME
laboratories to distribution offices/site of work.
131.15 Meters and CTs of matching ratio: All
out efforts may be made to install the meters and CTs of the same current ratio
so as to eliminate the multiplying factor.
131.15.1 Multiplying factor to be indicated in red ink: Where
meters and CTs of different current ratio were/are installed due to reasons of
non-availability of matching CTs, the multiplying factor must be indicated in
red ink on the consumer case, meter reading book(Kalamju) and ledger so that it
could be applied correctly. It
should also be written in indelible ink on the meter. AE./AEE/XEN should have a
consolidated record for all industrial and three phase connections in a bound
register for all such connections which have multiplying factors. Such register should be updated whenever there is any change in the
metering or CTs.
131.16 Performance of Mis: A proper control should be exercised on the
work of Meter Inspectors who should submit their reports to AE./AEE/XEN(Ops). daily. Points raised by the
Meter Inspector should be immediately attended to by AE./AEE/XEN(Ops). who is responsible for immediate compliance within 24 hours. However, the Meter Inspector should bring serious and suspicious cases to
the notice of the Sr.XEN/ASE(Ops) also.
131.17 MDI readings: The Meter Cup Board/metering terminal seals be checked
frequently especially in the case of major consumers,. SR.XEN./ASE (Ops) shall arrange surprise /secret recording of MDI reading before scheduled
reading dates.
131.18 Checking unauthorized load of TW Connection: For tube well consumers
intensive periodical checking should be carried out by the Operations/
Enforcement Staff. The enforcement staff should check dimensions of motors as
per ISI standards in case of motors which are manufactured in accordance with
these specifications, the current rating with clip on ampere meter on ' no load'
or 'full load' after tube well is operated for some time and comparing it with
the name plate particulars of the motors, unauthorized extensions and misuse of
energy.
131.19 In order to detect whether in single phase connections, the consumer has
not interchanged the neutral and phase lead, the meter Inspector should put on
heavy load to see whether the meter is functioning properly or not. JE/AAE
should be able to detect such cases.
131.20 Action against employees: Unscrupulous persons tap PSEB
mains/sub-mains unauthroizedly to feed their loads. Intensive raids both by the Enforcement and Operation staff should be
conducted in the areas infested by theft of energy. Deterrent punishment within the frame work of rules should be inflicted
on those employees who are found conniving in theft of electricity.
132. ADDITIONAL PRECAUTIONS IN RESPECT OF BOARD EMPLOYEES:
132.1 The officers Incharge of substations and colonies has a special
responsibility in the matter. He
will be personally responsible for any case of theft of energy specially if the
report is received from other sources.
132.2 In the Board's colonies a separate feeder for residences should be run
and a KWH meter installed at the sending end to register the entire residential
consumptions. A monthly comparison
be made between the readings of this KWH meter with the total consumption by the
Board's employees residing in the quarters.
132.3 Following checks on the meters of the employees should be exercised by
the various officers/officials:-
132.3.1 The initial sealing of meter terminal cover may be done by JE who will be
held responsible in case of wrong connections.
132.3.2 Meter Inspectors should check the meters of all the employees residing in
the towns, atleast once in 2 months and ensure that they are in working order,
seals are intact and no means are being employed for stealing energy. Cases of low consumption should be investigated and report submitted to
the AE./AEE/XEN.
132.3.3 AE./AEE/XEN(Ops). concerned
should also exercise checking of the meters and the service lines of the Board
Employees as given below and seal the meters in token of check:-
132.3.3.1 Employee staying in the PSEB Colonies :Once in Two Months
132.3.3.2 All other staff staying in town. :5% every month
132.4 The Meter Inspector will keep the readings of the meters installed at the
premises of Board employees taken by him separately in the Check Register and
put up for scrutiny to the AE./AEE/XEN(Ops). who will compare them with the normal consumption expected from the
employees corresponding to status. In
the event of large discrepancy, matter should be investigated thoroughly and
Sr.XEN/ASE/SE(Ops) and the CE(Ops) apprised of the position for further action.
133. DISPOSAL OF THEFT OF ENERGY CASES/REGISTRATION OF FIR:
133.1 The AE/AEE(Ops) , SRXEN/ASE(Ops) is authorized to lodge' First
Information Reports" with the Police and launch necessary prosecution on
behalf of the Board under section 50 of the Indian Electricity Act,1910, for
cases constituting theft of energy as described under section 39 of the Act read
with Condition No.43 of Conditions of Supply or where fake/tampered seals are;
detected or where ME seals are found broken/missing and removed and meter cover
can be opened and actual consumption recorded leads to the conclusion that the
consumer has been indulging in theft of energy.
133.1.1 In all cases where theft of energy is detected unambiguously by the
Enforcement/operation organization in respect of industrial connection above 500
KW and NRS connections above 100 KW, it will be decided with the specific
approval of "Director (Enforcement) or Dy.CE/SE(Ops) concerned( as the case
maybe) as to whether only compensation is to be levied on Fir is also to be
lodged with the police for criminal proceedings. Purpose of these instructions is to allow levy of compensation in minor
violations but in case of established theft case i.e. by passing of meters,
tampering of seals etc. where evidence for conviction is available, compensation
should be levied in addition to lodging FIR with the police with the approval of
the competent authority . In case
of any doubt, the matter may be referred to Chief Engineer(Comml.)
FIR cases shall be followed up by Administrative Member to whom necessary
details shall be supplied by the concerned agency immediately on the occurrence
of such events. Such police cases
shall also be reported to the Board every three months.
133.2 Whenever it is established to the satisfaction of the Board's Authorized
officers that a consumer has indulged in theft of energy through any of the
means mentioned in condition No.43(quoted hereunder) of the Conditions of
Supply, the Board may without prejudice to its other rights cause the supply to
the consumer discontinued without any prior notice to the consumer.
43.1 A
consumer or any person shall be guilty of theft of electric energy and shall be
deemed to have committed theft within the meaning of the act, the Indian Penal
Code where he maliciously causes energy to be wasted or diverted or dishonestly
abstracts, consumes, uses, draws any energy;
43.1.1 otherwise than through a
meter referred to in condition No.22 of 'Conditions of Supply' or Section-26 of
the Act, or
43.1.2 through any artificial mean or means not authorized by the Board or
43.1.3 by tampering with such meter or its body seals or apparatus or circuits,
or
43.1.4 by manipulating such meter, indicator or apparatus referred to in sub
section(7) of Section 26 of the Act and condition No.22 and 23 of Conditions of
supply or
43.1.5 by manipulating or abstracting or interfering in the functioning of such
meter in any manner so as to prevent it from fully and/or correctly registering
the energy consumed, or
43.1.6 by manipulating change of
phase of electric supply lines, or
43.1.7 from
a disconnected service if the consumer prevents registration by the meter of the
energy abstracted, consumed, used or drawn or.
43.1.8 by any other means whatsoever interfering with the said meter and the
connected wiring, CTs and PTs or Board's works where such interference is an
offence Under Section-44 of the Act .
43.1.9 In
the case of an agriculture consumer by increasing the Horse Powerage of the
motor or by in any way using the electricity for residential or industrial or
poultry/fish farming etc.
134. WORKING OUT COMPENSATION OF LOSS ARISING OUT OF THEFT OF ELECTRICITY:
Recovery
of compensation for the loss sustained by the Board as a result of theft of
energy shall be made as per the provisions of Conditions No.43.4 and 43.4.1 of
C.O.S and Para-5(quoted hereunder) of the Schedule appended to COS.
43.4 Levy of Compensation: Where it is established to the satisfaction
of the Authorized Officer(s) of the Board that a consumer has indulged in theft
of energy, the Authorized Officer of the Board may without prejudice to other
rights, direct the consumer to compensate the Board for the loss caused to it as
a result of theft of electricity and also to pay one time additional ACD at the
rate prevalent at the time of theft of electricity.
43.4.1 Rate of Compensation:: Compensation will be levied at the rates
and terms described in the Schedule or as prescribed
by the Board from time to time.
"5 Compensation of
Theft of Electricity: A
consumer found by the authorized
officer to have indulged in theft of electricity shall pay the compensation at
the following rates or the rates and terms as prescribed by the Board from time
to time.
|
|
Category of Consumers
|
|
Rate
|
|
5.1
|
Domestic Supply upto
3 KW
Above 3 KW
|
:
|
Rs.500/- per KW
Rs.1,000/- per KW
|
|
5.2
|
NR Supply(Loads up to
20 KW)/SP supply
|
:
|
Rs.1000/- per KW
|
|
5,3
|
NRS/(Load above 20 KW
and up to 100 KW)/ MS Supply
|
:
|
Rs.2000/- per Kw
|
|
5.4
|
NRS(Above 100 KW) and
Large Supply
|
:
|
Rs.2,500/- per KW
|
|
5.5
|
Tube well(AP) Supply
|
:
|
Rs.1,000/- per BHP
|
5.5.1 Suitable compensation in case of theft involving changes in the counter gear/pressure coils/current coil(s) with higher
ratio of a meter shall be worked out by over hauling accounts for such consumers
taking maximum period of two years from the date of checking or one time fixed
compensation charges to be worked out the load (as per prevailing instructions)
for theft of energy as per the rates mentioned above in clause 5.1 to 5.5
whichever is more.
5.6 In
case of BS category of consumers, compensation amount shall be worked out as per
rates specified under paras 5.2 to 5.4 on the basis of sanctioned load.
5.7 In
respect of LS/BS consumers, reconnection, amount as worked out @ 33% of the
compensation amount shall be subject to a maximum of Rs.50 lacs.
5.8 Compensation
amount in respect of all categories except DS/NRS shall be worked out on the
basis of sanctioned load and not the actual connected load found at site. Where an unauthorized load is also detected, load surcharge at the
prevailing rates shall be levied. The
kun-authorized load detected , if any, shall be got disconnected.
5.9 The
compensation amount in case of DS/NRS category of connections shall be worked
out on the basis of actual connected lod or sanctioned load whichever is higher
in addition to levy of load surcharge on the unauthorized portion of the
connected load.
5.10. Deleted.
5.11 The
unauthorized load in case of al the DS./NRS category of consumers shall be
compulsorily regularized after obtaining fresh A&A forms alongwith security
and service connection charges before allowing
reconnection. For the execution of
said instructions, it is necessary that actual connected load of DS/NRS
consumers may invariably be checked where theft of energy is detected.
5.12 In
addition to compensation as provided under Para 5.1 to 5.5 one time additional
ACD at current rates shall also be charged and recovered.
5.13 While
levying these charges on per KW basis, the amount of bills already charged is
not to be adjusted.
5.14 The
connection shall be disconnected immediately and shall be reconnected after
recovering the compensation and reconnection fee etc.
5.15 In
case of 2nd default(Theft of energy) occurring within twelve calendar
months of first detection at the same premises by the same consumer (except seasonal industries)
than the rates for working out compensation amount shall be doubled and the
factory/premises shall be disconnected for one week even if the default is not
falling within same financial year. For seasonal industries, if theft of energy
is detected 2nd time in a season, the compensation shall be worked out at double the rates and connection shall be disconnected
for one week even if the default is not falling within the same financial year.
5.16 ED shall also be charged on the applicable compensation as under:
Electricity duty =Amount Charged x Electricity duty rate per
unit
Chargeable Average rate of (as applicable)
energy per unit
134.1 Compensation should be levied where fake seals or tampered seals or
broken/missing seals enable the opening of the meter cover and actual
consumption recorded leads to the conclusion that the consumer has been
indulging in theft of energy. The consumer shall be asked to pay compensation
amount as per standing instructions applicable for theft cases. The cost of meter may also be recovered.
134.2 COMPETENT AUTHORITY TO LEVY THE AMOUNT OF COMPENSATION:
The compensation shall be charged
in established theft cases detected by Operation Officers or Enforcement agency
for various categories of consumers by AE./AEE/XEN(Ops).concerned as per provisions of
Reg.No.134 Sr.Xen/ ASE(Ops) for theft cases detected by operation officers and
Sr.XEN/ASE (Enforcement) for theft cases detected by Enforcement agency shall
ensure that compensation amount in all such cases is charged as per Reg.No.134.
134.3 The Operation Officers shall defend the cases in the Court(s) and help of
the Enforcement agency should be sought wherever considered necessary.
134.4 Bill Cum Notice of Assessment: Notice of Assessment will be issued
by AE./AEE/XEN(Ops). as per
Condition No.43.5(quoted hereunder) of the C.O.S.
"43.5
Assessed compensation and the amount of
AACD payable by the consumer shall be notified to the consumer in the form of a
bill cum notice within 48 hours from the date of checking/inspection requiring
the consumer to show cause as to why the assessed compensation be not recovered
from him.
43.5.1:
Such bill cum notice interalia mention the matters relating to the act of
malpractice or theft of energy noticed by the Authorized Officer during
inspection of the installation/equipments in the premises of the consumer and
details of the amount billed to him will also be supplied.
43.5.2: A copy of
memorandum of inspection and seizure shall also be enclosed with the notice if
it had not been delivered to the consumer or his representative after the
checking/inspection by the Authorized Officer.
43.5.3: The Officer serving the bill-cum-notice shall inform the
consumer to contact the Dy.CE/SE(Ops.)/ CE/(Ops) for restoration of supply to
his premises as per competency.
43.5.4:
On receipt of representation/reply to the show cause notice, if any XEN/AEE/AE(Ops)
concerned will send the assessment case alongwith the representation to the
Addl.SE/Sr.Xen(Ops).
43.5.5: The Addl. SE/Sr.Xen/Op. will inform the consumer of the
date, venue and the authority who will review the assessment made in the light
of his representation in order to enable him to represent his case personally or
through an authorized representative."
134.5 Competent Authorities to carry out inspection , make assessment of
compensation have been described in Para-2 of the Schedule of COS(reproduced
below):-
"2
Authorized Officers: Following
officers of the Board shall be competent to carry out checking/ inspection and
testing of the electrical installation at the consumer's premises:-
|
S.No.
|
Category
of Connections
|
|
Authorized
to Enter and Inspect
|
|
OPERATION OFFICERS:
|
|
|
|
1.
|
All
Domestic/Non Residential Connections
|
:
|
JE/AAE/AEE/XEN
|
|
2.
|
Small
Power/Bulk Supply Connections up to 20 KW
|
:
|
-do-
|
|
3.
|
Medium
industrial/Bulk Supply Connections up to 100 KW
|
:
|
AE/AEE/XEN/Sr.XEN/Addl.SE
|
|
4.
|
Large
Supply and Bulk Supply Connections (Above 100 KW)
|
:
|
AE/AEE/XEN/Sr.XEN/Addl.SE
|
|
ENFORCEMENT
OFFICERS:
|
|
|
|
1.
|
Loads
up to 500 KW
|
:
|
AEE/XEN/Enforcement
|
|
2.
|
Loads
above 500 KW
|
:
|
Sr.XEN/Addl.SE(Enforcement)
|
|
MMTS
OFFICERS:
|
|
|
|
1.
|
Medium
Supply/Large Supply and Bulk Supply
|
:
|
Sr.XEN/Addl.SE/MMTS
|
2.1 : Officers
authorized to make assessment of compensation: Following officers of the Board
shall be competent to approve the calculations and arrive at the amount of
compensation chargeable to the consumers as a result of checking and inspection
of the metering equipment and the electrical installations at the consumer's
premises:-
|
S.No.
|
Category
|
Assessed
Amount
|
Competent
Authority
|
|
1.
|
DS,NRS,SP
and Tube well Connections
|
i) Up to Rs.10,000/-
ii)Exceeding Rs.10,000/- and up to Rs.25,000/-
iii)Above
Rs.25,000/-
|
AE.AEE/XEN/(Ops)
ASE/Sr.Xen(Ops)
ASE/Sr.Xen(Ops)
and Sr.Xen (Enf.) shall jointly
assess and approve the calculations and in case of difference of opinion,
Dy.CE/SE (Ops) shall be the
assessing Authority
|
|
2.
|
MS,LS
& BS Connections
|
i) Up to Rs.25,000/-
ii)Exceeding Rs.25,000/-and up to Rs.1,00,000/-
iii)Above
Rs.1,00,000/- and up to Rs.10 lacs
iv)
Above Rs 10 lacs
|
AE.AEE/XEN/(Ops)
ASE/Sr.Xen(Ops)
ASE/Sr.Xen(Ops)
and Sr.Xen (Enf.) shall jointly
assess and approve the calculations and in case of difference of opinion,
Dy.CE/SE (Ops) shall be the
assessing Authority
Director(Enforcement)
and Dy.CE/SE(Ops) shall jointly assess the case and approve the
calculations and in case of difference of opinion, CE/ (Ops) shall be the assessing Authority
|
2.2:
Copies of the approved calculations shall be retained in the office of the
Competent Assessing Authority and shall also be sent to the next higher office
for record.
2.3:
Officers senior in rank and having jurisdiction in concerned area shall also
have the powers mentioned under Column (iii) and (iv)."
135. RELEASING OF A NEW CONNECTION TO A PERSON INVOLVED IN THEFT OF
ELECTRICITY:
Unauthorized installation in such cases shall be permanently disconnected
from Board's system and release of regular connection in such a case shall be
governed by following conditions:-
135.1 If any person or a prospective consumer is found stealing energy without
his connection having been released officially, he shall pay the amount of
compensation charges as worked out on the basis of detected load and as per
rates applicable from time to time.
135.2 For general category of tube-well applicants release of regular
connection shall be allowed on its
turn under the applied category after recovering charges as per terms and
conditions of SFS. For other AP priority category (to be released under SFS)
connection shall be released after re-assigning the seniority by taking the
deemed date as six months after the actual date of registration.
135.3 For General, Industrial and Bulk Supply applicants only seniority shall
be reassigned by taking the deemed date of registration of application six
months after the actual date of registration.
135.4 In order to obiviate the possibility of such consumers getting the
electric connections at some other premises/place, electric connections(
new/extension) shall be refused/deferred to those consumers who were allegedly
found committing theft of energy in one premises and seek connection(new/extension)
in the same/different name and style till such time consumers make payment of
the compensation charges alongwith AACD as intimated to them or dispute is
settled by the Court/DS and Reviewing Authority/Arbitrator as the case may be.
135.5 New Connection/Extension in load to such persons or consumers who are
found indulging in theft of energy shall be released only after payment of
atleast 50% compounding charges or as per directions of the special court if
such an applicant has not agreed to pay the compounding charges. An undertaking to deposit the balance compounding charges as per decision
of the Appellate Authority/Arbitrator shall be submitted by such applicant.
136. RECONNECTION OF SUPPLY TO CONSUMERS CAUGHT STEALING ENERGY:
136.1 Reconnection where FIR is lodged:
Premises
of a consumer who has been caught stealing energy either by the Sr.Xen/ASE(Enforcement)
or the Operational staff and whose case has been handed over to the Police for
investigation and prosecution, will be reconnected if a specific request is
received from him and he fulfills the following formalities:-
136.1.1 Those parts of the Board's/Consumer's installation which are required to
be removed for evidence by the Police, may be removed and their substitutes
provided by the respective owners(Board or consumer) to whom these parts
belongs.
136.1.2 An undertaking be obtained from the consumer that the connection of his
premises will be without prejudice to the case instituted against him by the
Board/ the Police and subsequent trial in the Court of law and decision thereof.
136.1.3 One time additional ACD at the current rates will be got deposited.
136.1.4 Consumer shall pay to the Board, the amount of compensation as per
provisions of Condition No.43.6 of conditions of supply reproduced below:-
"43.6:- Reconnection of Supply:- Engineer-in-Chief/Chief
Engineer/Ops (where the assessed compensation exceeds Rs.1 Lac and Dy.CE/SE(Ops)
(assessed compensation amount up to Rs..1 Lac can allow restoration of supply
after accepting a part of the assessed compensation as under:-
Assessed compensation including AACD : Amount of part payment
1. Up to Rs. 1 lac : 33% of the
Assessed compensation
2. Exceeding Rs.1 lac
: 33% of the Assessed compensation
subject to a maximum of Rs.50 lacs
43.6.1:- If the consumer is unable to make the
part payment as prescribed in the preceding Para and the Engineer-in-Chief/CE(Ops)
is of the view that further relaxation is called for on the facts and
circumstances, such a case shall be promptly put up to the Spot Review
Committee, after getting approval of Member Incharge Commercial Organization. The consumer shall be informed of the minimum amount which he is required
to deposit for securing reconnection of supply.
43.6.2 :- In order to expedite the
reconnection of supply the consumer may contact the CE /Dy.CE/SE/ (Ops) after
the office hours or even on holiday/non-working days.
43.6.3:- As soon as the consumer makes the payment of a part of the assessed
amount of fine as communicated by the CE/SE/Dy CE(Ops) and the reconnection fee,
his premises will be reconnected expeditiously.
136.2 Laxity in sealing the meters: Operation Officers/Officials who are
required to affix and check the seals of metering equipment should taken due
care while affixing seals. n case
the seals affixed by them are found to be intact by Enforcement Staff/Checking
authorities, but the consumer is found to be indulging in theft of energy or
meter is found to be recording less due to wrong connections, this situation
shall betaken as intentional connivance of such officer/official and he will be held fully responsible for the consequences thereof. Without prejudice to above suitable disciplinary action should be taken
against the officer/official concerned as per normal rules.
136.3 Reconnection of supply to industries producing perishable goods:
if a consumer dealing with perishable goods e.g. cold storage caught indulging
in theft of electricity makes a request for review of the compensation amount
and restoration of supply, the review should be completed within 24 hours from
the receipt of the request to avoid damage to goods. Similarly for continuous process industries disconnection maybe avoided
for the Ist default if the consumer pays onetime AACD and 50/33% of the amount
of compensation assessed. In case
the connection has been disconnected, reconnection maybe allowed in terms of
Para 136.1
136.4 Reconnection of Supply after 2nd and subsequent default:
Depending upon the merits of the case FIR may invariably be lodged in respect of
a consumer who is repeatedly found to be indulging in theft of energy. Supply for 3rd and subsequent defaults should be restored
after the full payment of the provisionally assessed compensation and atleast
100% additional ACD at the prevalent rates.
136.4.1 In such a case the consumer should also be informed that if there is any
further repetition of the offence, it shall entail termination of the agreement
under condition No.20.5 of the C.O.S.
136.5 Seizure of Evidence: Although the supply shall be restored after
the consumer has made the payment as per the preceding paras and has also
complied with the formalities yet the artificial means including metering
equipment where cases of tampering of meters/ME seals are involved shall be kept
in " AS FOUND CONDITION" in safe custody of AE./AEE/XEN(Ops). till the final decision of the case.
136.5.1 All the meters removed against any meter change order(MCO) shall be sent
to ME Labs, in the sealed card-Board box duly signed by concerned PSEB
officers/official and the consumer or his representative. In case the consumer refuses to sign the meter test results/report, such
meter shall be kept in the sealed box by the AE./AEE/XEN(Ops). operation
till the final disposal of the case. If the consumer deposits the compensation amount without
going to the Dispute Settlement Committee or Civil courts such sealed meter
shall be returned to the ME Lab.
Similar procedure shall be adopted in case of meters sealed by the
Enforcement Agency/Operation Organization in theft cases.
137. PREJUDICIAL USE OF SUPPLY, RESALE OF ENERGYAND MALPRACTICES:
137.1 Prejudicial use of Supply:- In terms of condition no.40 (reproduced
below) of the COS following acts on the part of the consumer shall constitute
prejudicial use of supply.
40.1 he
keeps connected to the Board's supply system any apparatus which the Board may
deem to be likely to interfere with or effect injuriously the Board's supply to
other consumers.
40.2 he
keeps except in the case of domestic supply and also except to the extent herein
prescribed unbalanced loading on the three phases of the supply taken by him
from the Board, the maximum permissible difference in current between any two
phases being 5 percent.
40.3 he makes such use of the supply given to him by the Board as to
interfere with the safety or efficient working of the Board's supply lines or
other works or to act prejudicially to the Board in any manner whatsoever.
40.4 any AP/Industrial
consumer is found running his three phase motor(s) for tubewell/industrial
purposes during the period when single/two phase supply is provided in rural
areas for lighting/fans, the supply shall be disconnected forthwith. The penalty @ Rs.400/- per BHP shall be levied before restoration of supply.
137.1.1 A consumer classified in a particular schedule of tariff found using
electricity for a purpose for which rate of tariff is higher than that at which
the load was released shall be called upon to:-
137.1.1.1 Disconnect higher tariff load and submit test report.
137.1.1.2 Pay on higher tariff for the electricity consumption corresponding to the
load which otherwise would have been charged at the higher rate, for a period of
one year or from the last checking date of Flying Squad whichever is less. This shall apply to all cases except for the ones mentioned
in 137.1.1.3 & 137.1.1.4 below:-
137.1.1.3 An Industrial consumer who has unauthorized load and is charged load
surcharge under the relevant clauses of the tariff schedule, shall not be
required to pay at the higher tariff schedule for the energy consumption, if by
virtue of the unauthorized load the applicability of the tariff schedule
changes.
137.1.1.4 Also with the abolition of the extra charges for factory lighting the use
of industrial connection for colony/yard, security/guard room and a guest house
etc. forming part and parcel of the industrial unit shall not be covered under
prejudicial use of electricity but such a load if found in excess of the total
sanctioned load shall be required to be disconnected and shall call for levy of
load surcharge as per the instructions inforce from time to time.
137.2 Resale of Energy: Cases pertaining to resale of electricity shall
be disposed off in terms of condition No.41(reproduced below) of the C,O.S.
41:-Resale of Energy: No
consumer shall sell electrical energy supplied to him by the Board to any other
person without the prior written permission of the Board. However, collection of electricity charges by the house owners from the
tenants for residential purposes shall not be treated as violation of the
foregoing provisions. Use of electricity by more than one establishment in the same
premises as provided under condition No.19.4 shall not be deemed as resale of
electricity.
137.3 Malpractices: Cases pertaining to malpractices shall be disposed off in
terms of condition No. 42(reproduced below), 44 of the C.O.S already reproduced
in Para 133 and Para No.4 of the schedule reproduced hereunder:-
42:- Malpractices: A consumer shall be guilty of an act of malpractice with reference to
the use of electric energy supplied by the Board:
42.1: Where
he uses energy in contravention of any provisions of the Indian
ElectricityAct,1910 or of the Electricity(Supply) Act, 1948 or any of the rules
or regulations made under these acts or of any contract made under these
conditions, as relate to or regulate the supply of energy to the Board,or
42.1.1:-Where
he fails to take adequate measures to check pollution of electric supply due to
harmonics generated in the induction/arc furnace etc.
42.2:- Where
he engages unauthroizedly in the supply of electricity to any service
disconnected by the Board, or in the illegal restoration of his own service
disconnected by the Board or
42.3:-
where in categories of non-domestic supply, bulk supply he connects extra load
unauthroizedly . However,
industrial consumers making unauthorized extensions to the extent mentioned
hereunder, or that prescribed under the board from time to time, will not be
disconnected and will not be subjected to load surcharge.
42.3.1:-LS
consumers-10% of sanctioned load subject to maximum .of 250 KW
42.3.2:MS
consumers-10% of sanctioned load(for consumers with sanctioned load up to 90 KW)
42.3.3: SP
consumers-10% of sanctioned load(for consumers with sanctioned load up to 18 KW)
42.3.4:For
MS and SP consumers with sanctioned load above 90 KW and 18 KW, the extra load
permissible will be to the extent that the sanctioned load together with the
unauthorized load does not exceed 100 KW and 20 KW respectively.
42.4
Where he does not comply orders imposing restriction on use of electricity
either during peak load hours or during any other period.
42.5
Where he keeps connected to Board's supply system any apparatus or adopts any
electrical appliance for the purpose of splitting the phase to run his three
phase appliances when the Boards three phase supply is not available to him.
42.6:Where
he uses electricity supplied under a particular tariff for a purpose for which
some other tariff is in force, or.
42.7:Where
without the permission of the Board extends the Board's supply to any premises
other than the premises to which the supply is given or to any consumer/unit
within the same premises. Provided,
that the extension of Board supply for a religious or non commercial social
function of the consumer himself not exceeding three days, shall not be
considered a malpractice.
42.8:Where
in violation of Condition No.41 he sells or otherwise supplies energy to any
other person without the permission of the Board. Provided, that the collection
of electricity charges by the owner of the premises(consumer) from his tenant
under domestic, non-domestic and bulk supply shall not be considered as a
malpractice.
42.9:Where
he assigns, transfers or parts with the benefit of the agreement with the Board
or creates any partial or separate interest thereunder:-
42.10:Besides
disconnection of supply as provided in the Schedule, the consumer shall also be
liable to compensate the Board in terms of the provisions of conditions No.43.3 to 43.10 read with the schedule."
"4
Compensation for Violations/Malpractices: Only
those violations /malpractices for which compensation/surcharge has not been
;provided in the Schedules of Tariff but for which compensation charges or extra
levy are payable by consumers are dealt with in this schedule. However, compensation charged for violation/malpractices covered under
the Schedule of Tariff will be subject to review/appeal as per the provisions of
the Schedule.
4.1 Compensation for Malpractices not covered under Schedule of Tariffs: A
consumer shall pay compensation charges for the following malpractices covered
under condition Nos.41 and 42 of "Conditions of Supply" as determined
by the Board.
Supply
of electricity from a live service connection to a disconnected service
connection.
Unauthorised
supply/resale of electricity as defined under condition No.41
Unauthorized
extension/shifting to any premises other than that for which supply is given.
The
violation should be removed within 48 hours from the receipt of the notice and
compliance reported to the AE./AEE/XEN(Ops). concerned The consumer
should compensate the Board by making payment @ Rs.750/- ( or as revised from
time to time) per K W or a part thereof of the unauthorized load.
Supply
of electricity from a tube well connection to a disconnected connection.
Unauthorized
supply/resale of electricity from a tube well connection.
Unauthorized
shifting of connection to a premises other than that of the consumer. The connection maybe disconnected under intimation to the consumer. If requested by the consumer, it may be restored to its original site
after the consumer pays the re-shifting charges.
Where
the consumer assigns, transfers or prts with the benefits of the connection
unauthroizedly, the consumer should be served with a notice of 7 days to remove
the violation failing which he may be billed at a rate 50% in excess of the
normal tariff applicable to him. 50% higher charges shall continue until the
malpractice is stopped or the Board regularizes the action of the consumer.
4.2 Procedure for recovering the compensation charges and removal of
malpractice:
4.2.1 On detection of violation/malpractices covered under Condition No.41,42
the AE./AEE/XEN(Ops). will issue
supplementary bill-cum-notice to the consumer to remove the violation within 48
hours under written intimation to him failing which the supply shall be
disconnected without any notice. The consumer should also be asked to show cause within 15
days as to why compensation charges intimated to him should not be levied to him
and recovered for having committed the malpractice. Reply to show cause notice
shall be sent by the consumer within 15 days from the receipt of the notice.
4.2.2 If the consumer fails to remove the violation within 48 hours, supply to
his premises should be disconnected promptly. It should not be restored unless he removes the violation and deposits
33% of the compensation amount as is applicable for theft of electricity cases.
4.3 Review and Appeal: Procedure outlined in Condition No.44 shall be
applicable.
4.4 Multiple Violations: if a consumer commits more than one violation/
malpractices, at the same time, he
shall be liable to pay compensation for each of them separately.
137.4 Discontinuance of Supply: Discontinuance of Supply in the event of
prejudicial use of supply/malpractices will be regulated by the provisions of
Condition No.35.3( reproduced hereunder) of COS.
35.3.1 : Whereon an inspection made
under Condition 40,42 and 43 the Authorized officer is of the view that the
consumer has committed an act of prejudicial use of supply, malpractice, or
theft of energy, the Authorized officer shall have the authority to disconnect
the supply of energy to the consumer forthwith and without any notice to the
consumer, provided that no such disconnection shall be made.
35.3.1.1: Where the act of malpractice committed by the consumer falls
under the malpractice defined under condition 42.6 to 42.10 without serving a 48
hours or 7 days notice, depending upon the urgency of the matter, upon the
consumer to stop the commission of the malpractice, and if the consumer does not
comply with the requirement of the notice, the disconnection shall be done
without any further notice.
35.3.2 :Save as otherwise provided
in Para 35.3.1.1 above, the service of a consumer disconnected under clause 35.3
above shall be reconnected upon.
35.3.2.1: Payment by him to
the Board an amount equal to 100% of ACD(as communicated by the Board)
applicable to him as per present rate and 33% of the assessed compensation
amount, subject to maximum of Rs.50 lacs.
35.3.2.2: Compliance by him with such directions for the discontinuance
of the act of malpractice, or theft of energy as the case may be, as the
Authorized officer may, by order in writing, communicate to the consumer in this
behalf.
35.3.2.3: Reconnection of supply for cases covered under Para 42.6 to
42.10 will be carried out after the consumer has ceased to default to the
satisfaction of the Board.
137.5 Compensation admissible for prejudicial use of Supply: Board will
be entitled to compensation in terms of Condition No.34 of COS in the event of
any damage caused to the Board's apparatus owing to default on the part of the
consumer in terms of condition No.40 and 42.
138. RECORDING OF CASES OF THEFT OF ENERGY/MALPRACTICES:
138.1 Monitoring of levy and recovery of compensation amount: in order
to monitor the compensation recoverable from the consumer on account of
detection of theft of energy,
entries of compensation amount be made in a job control register(JCR) to be
maintained in the operation sub-division. JCR will be issued from the divisional office, the record of
which will be maintained like S.M.B. This
register will be properly numbered at the time of issue and attested by Sr.XEN/ASE
. The entries in the JCR shall be
made as per the prescribed proforma. After the entries are recorded and signed by the concerned officer, the
notice shall be served to the consumer by the AE./AEE/XEN(Ops). for depositing the required compensation amount under intimation to
Sr.XEN/ASE(Ops)/ SR.XEN/ASE(Enf.)/ O/Field/Sr.XEN/ASE CBC) and SE/DCE(Ops)/Enforcement.
138.1.1 All recoveries effected from the consumer shall be recorded in the JCR. Till such time the entire assessed amount is realized, the same shall be
considered as a disputed amount and shall be reflected as such. A return of al such cases shall be submitted every month
through the SE./DCE(Ops) to Director Enforcement, Chief Engineer Enforcement and
CE(ops) on the prescribed proforma. This
return shall for a part of MIR and shall be reviewed by the Board in its
periodical meetings.
138.2 This register shall be handed over by the concerned official/officer to
his successor.
138.3 Inspecting officers during their inspection shall ensure that these
registers are being maintained and proper follow up action is being taken
expeditiously.
138.4 The compensation amount shall be debited to the consumer through a
separate bill after recording necessary entry in the sundry charge and
allowances register (SOP-6). The
recoverable amount shall be split up for the current year and the previous year. The amount shall be considered as disputed amount until the same is
deposited by the consumer. In theft
cases where the consumer has gone to the court and has obtained stay orders
against the recovery. the entire
amount shall be shown as disputed amount. However, in cases where the consumer
has opted for settlement through DSC, 33% amount or as decided by the competent
authority shall be recovered through SC &A register and the balance amount
shall be shown as disputed amount till the decision of DSC and payment by the
consumer.
138.5 SE/Dy.CE Ops concerned shall maintain list of such consumers in respect of Agricultural and Industrial consumers. For other categories the list shall be maintained by AE./AEE/XEN and
Sr.XEN/ASE(Ops) concerned.
139. RESPONSIBILITY OF OPERATIONAL STAFF TO CHECK 'THEFT OF ENERGY':
139.1 Officer/Officials(Ops) who are required to check and seal the metering
equipment should taken due care while affixing seal to the meter/metering
equipment. If the seals affixed by
them are found to be intact by Enforcement Staff./Inspecting Officer(s) and the
consumer is found to be indulging in theft of energy or meter is found to be
recording lower consumption due to wrong connections, it shall be taken as
intentional connivance of such an
officer/official and he will be held fully responsible for the consequences thereof. Disciplinary
action, as permissible under rules, shall be taken against the said
officers/officials.
139.2 The following officers/officials will be held responsible with respect to
the specified category of connections as detailed below-
|
139.2.1
|
All Single phase connections and metered AP connection
|
:
|
Meter reader/Meter Inspector /LM responsible for attending the
complaint/JE/AE
|
|
139.2.1
|
Three phase domestic /non residential connections without CTs/PTs
connections of Board employees, street lighting and SP connections.
|
:
|
Meter reader/Meter Inspector/L.M. responsible for attending the
complaint AE/JE/AAE/AEE/XEN(Ops)
|
|
139.2.3
|
Non Residential connections with CTs/PTs, Bulk Supply connections
released on LT, MS connections(with or without CTs/PTs and MDIs of all LS
consumers)
|
:
|
JE/AAE/AE./ AEE /XEN(Ops).
|
|
139.2.4
|
Large Supply and Bulk Supply connections above 500 KW/KVA
|
:
|
In addition to officers/officials under Para 139.2.3, Sr.XEN/ASE
(Enforcement and MMTS)
|
|